Product Type | Voltage (V) | AC/DC | Frequency (Hz) | Power (W) | Speed (rpm) | Flow Rate (m³/h) | Weight (kg) |
---|---|---|---|---|---|---|---|
CT 18.4 H | 380 | AC | 50 | 190 | 1445 | 1100 | 11.5 |
MODEL | C | D | E | H | L | O | P | S | T |
CT 18.4H | 312 | 180 | 280 | 395 | 167 | 140 | 110 | 130 | 145 |
Dündar Hot Environment Fans are centrifugal fans specially designed to handle temperatures up to 120°C. They are used for ventilating and cooling the current environment.
When selecting a fan, four main parameters should be considered:
The required air exchange for a space depends on the purpose of the environment, the number of people and objects within, and their activity levels. Below is a table of air exchange rates for various environments:
Environment | Air Exchange Rate (times/hour) |
---|---|
Auditoriums | 6-8 |
Paint Booths | 25-50 |
Vault Rooms | 3-6 |
Cinemas & Theaters | 5-8 |
Commercial Kitchens | 15-30 |
Foundries | 8-15 |
Gymnasiums | 4-6 |
Laundries | 10-20 |
Indoor Pools | 3-4 |
Restaurants | 8-12 |
Conference Rooms | 6-8 |
Waiting Rooms | 4-8 |
Copy Rooms | 10-15 |
Machine Rooms | 10-40 |
Shops | 4-8 |
Dry Cleaners | 5-15 |
General Manufacturing Areas | 4-8 |
Hospitals | 8-12 |
Laboratories | 8-15 |
Activity Type | Airflow per Person (m³/hour) |
---|---|
Normal Activity (Non-Smoking) | 29 |
Normal Activity (Smoking) | 58 |
Light Activity | 45 |
Heavy Activity (Industrial) | 60 |
The required airflow (Q) can be calculated as follows:
Consider an office with 5 people, a ceiling height of 2.6 meters, and a floor area of 50 m². The room volume is:
2.6 × 50 = 130 m³
From the air exchange table, the air exchange rate for an office is 4-8. Let’s take 5 as the rate:
130 × 5 = 650 m³/hour
For the people in the office, assuming normal activity:
5 people × 29 m³/hour = 145 m³/hour
The total airflow requirement would be:
650 + 145 = 795 m³/hour
After determining the airflow, consider the following: